{"id":12714,"date":"2024-03-20T12:15:20","date_gmt":"2024-03-20T11:15:20","guid":{"rendered":"https:\/\/b3v39j.myrdbx.io\/ul-wissen\/ul-wiki\/short-circuit-current-rating-sccr\/"},"modified":"2026-07-31T19:57:25","modified_gmt":"2026-07-31T17:57:25","slug":"short-circuit-current-rating-sccr","status":"publish","type":"wiki","link":"https:\/\/krayer.de\/en\/ul-wissen\/ul-wiki\/short-circuit-current-rating-sccr\/","title":{"rendered":"Short-Circuit Current Rating (SCCR)"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">The <strong>Short Circuit Current Rating<\/strong> (SCCR) is a U.S. term used to describe the <strong>testing of the short-circuit withstand capability of electrical <\/strong>systems.<\/p>\n\n<h2 id=\"bezug-zur-ul\" class=\"wp-block-heading\">Relation to UL<\/h2>\n\n<p class=\"wp-block-paragraph\">The UL 1449 standard, in conjunction with <a href=\"https:\/\/krayer.de\/en\/ul-wissen\/ul-wiki\/nfpa-79\/\">NFPA 79<\/a>, stipulates that a <a href=\"https:\/\/krayer.de\/en\/ul-wissen\/ul-wiki\/surge-protection-device\/\" data-type=\"wiki\" data-id=\"1495\">surge protection device<\/a> (SPD) is required when safety components are installed in the control cabinet. The SPD can be installed either on-site or inside the control cabinet. <\/p>\n\n<p class=\"wp-block-paragraph\"><div class=\"hw-ray\"><div class=\"hw-ray__text\"><\/p>\n\n<h2 id=\"das-sccr-kurzschlussfestigkeit-fur-den-amerikanischen-markt\" class=\"wp-block-heading\">The SCCR: Short-Circuit Resistance for the U.S. Market<\/h2>\n\n<p class=\"wp-block-paragraph\"><strong>All control cabinets<\/strong> and other electrical systems intended for use in the United States or Canada must <strong>be rated for short-circuit current <\/strong>in accordance with <strong>Article 409 of the 2005 National Electrical Code<\/strong> (NEC 409). This rating is referred to as <strong>the Short Circuit Current Rating<\/strong> (SCCR).   <\/p>\n\n<p class=\"wp-block-paragraph\">The goal of the amendment to the law was to improve workplace safety, particularly by preventing short-circuit arcs. The maximum value of the short-circuit current is referred to as <strong>short-circuit withstand capacity.<\/strong> This must be at least as high as the highest possible <strong>fault current<\/strong>, or higher. <\/p>\n\n<p class=\"wp-block-paragraph\"><\/div><div class=\"hw-ray__media\"><img src=\"https:\/\/krayer.de\/wp-content\/uploads\/2024\/03\/ray_nachdenklich_wiki.webp\" alt=\"Ray, the Krayer Systemtechnik mascot, with a thoughtful expression\" width=\"150\" loading=\"lazy\" decoding=\"async\"><\/div><\/div><\/p>\n\n<h2 id=\"was-hat-das-sccr-mit-der-ul-508a-zu-tun\" class=\"wp-block-heading\">What does the SCCR have to do with UL 508A?<\/h2>\n\n<p class=\"wp-block-paragraph\">The <strong>requirements for short-circuit protection<\/strong> are defined in NEC 409. In response to the amendment to NEC 409, Underwriters Laboratories has updated its <a href=\"https:\/\/krayer.de\/en\/ul-508a\/\"><strong>UL 508A<\/strong> <\/a>with <strong>Appendix <em>SB<\/em><\/strong>. This appendix incorporates the requirements of NEC 409 into the UL standard. This ensures that a <a href=\"https:\/\/krayer.de\/en\/ul-wissen\/ul-blog\/where-is-the-control-cabinet-ul-certified\/\">UL-certified control cabinet meets all legal requirements, including <\/a>those for short-circuit resistance.   <\/p>\n\n<figure class=\"wp-block-image size-full is-resized\"><img fetchpriority=\"high\" decoding=\"async\" width=\"820\" height=\"461\" src=\"https:\/\/krayer.de\/wp-content\/uploads\/2024\/04\/ul-zulassung-0.png\" alt=\"Short-Circuit Withstand Capacity (SCCR) Using the UL Control Cabinet as an Example\" class=\"wp-image-6013\" style=\"aspect-ratio:1.7777777777777777;object-fit:cover;width:1312px;height:auto\" title=\"SCCR - Short-Circuit Resistance Requirements\" srcset=\"https:\/\/krayer.de\/wp-content\/uploads\/2024\/04\/ul-zulassung-0.png 820w, https:\/\/krayer.de\/wp-content\/uploads\/2024\/04\/ul-zulassung-0-768x432.png 768w, https:\/\/krayer.de\/wp-content\/uploads\/2024\/04\/ul-zulassung-0-300x169.png 300w\" sizes=\"(max-width: 820px) 100vw, 820px\" \/><\/figure>\n\n<h2 id=\"wie-funktioniert-ein-short-circuit-current-rating\" class=\"wp-block-heading\">How does a short-circuit current rating work?<\/h2>\n\n<p class=\"wp-block-paragraph\">The operator of a system is responsible for <strong>complying with <\/strong><a href=\"https:\/\/krayer.de\/en\/ul-wissen\/ul-wiki\/safety-engineering\/\">occupational safety regulations<\/a>. This also includes ensuring that its electrical equipment has sufficient short-circuit withstand capability. The law requires that a separate short-circuit current rating be performed for <strong>each control cabinet <\/strong>that controls a machine or part of a machine. The results of the SCCRs for the individual control cabinets are, in turn, essential for <strong>determining the short-circuit resistance of the entire machine<\/strong> or system (\u201cThe weakest link determines the strength\u201d).   <\/p>\n\n<p class=\"wp-block-paragraph\">In addition to the very time-consuming process of <strong>individually analyzing and designing each control cabinet configuration<\/strong>, there are two methods available for determining a control cabinet\u2019s short-circuit withstand capability:<\/p>\n\n<h3 class=\"wp-block-heading\"><em>Coordinated Selection<\/em><\/h3>\n\n<p class=\"wp-block-paragraph\">Under <strong><em>Coordinated Selection<\/em><\/strong> refers to the design and manufacture of a control cabinet <strong>using components exclusively from a single manufacturer<\/strong>. The components are <strong>optimized<\/strong> by the manufacturer <strong>for use together<\/strong>, which primarily means that they all have <strong>the same short-circuit withstand capacity<\/strong> and are backed by <strong>documented testing<\/strong> (SCCR). To simplify the design process, the manufacturers in question provide catalogs of the relevant components and design software. The main drawback of this approach is the <strong>loss of all flexibility<\/strong>. Only those components designated by the respective manufacturers for use together may be installed.    <\/p>\n\n<h3 class=\"wp-block-heading\">Control Panel Construction in Accordance with UL 508A<\/h3>\n\n<p class=\"wp-block-paragraph\">Since <strong>UL 508A<\/strong>, as specified in the aforementioned Annex <em>SB<\/em>, also requires short-circuit withstand testing, a control cabinet designed in accordance with this UL standard also meets the SCCR requirements. A UL-certified control cabinet manufacturer can thus <strong>design<\/strong> cabinets <strong>flexibly according to its customers\u2019 requirements<\/strong> without having to perform a time-consuming and expensive individual test on each cabinet every time. <strong>Important to note:<\/strong> Unlike <em>Coordinated Selection<\/em>, while components <strong>with different levels of short-circuit withstand capability<\/strong> can be <strong>installed<\/strong> in a UL-certified control cabinet, the short-circuit withstand capability of the \u201cweakest\u201d component always determines the SCCR of the entire control cabinet. <\/p>\n\n<h2 id=\"was-passiert-wenn-die-kurzschlussfestigkeit-geringer-als-die-maximale-hohe-des-fehlerstroms-ist\" class=\"wp-block-heading\">What happens if the short-circuit withstand capacity is less than the maximum fault current?<\/h2>\n\n<p class=\"wp-block-paragraph\">If the short-circuit current rating test reveals that the component under test <strong>does not<\/strong> have the required short-circuit withstand capability, it may <strong>still<\/strong> be <strong>installed under certain circumstances<\/strong>. To do so, a suitable <strong>overcurrent protection device<\/strong> must be installed in the system in question. Such a device interrupts the circuit if a predetermined current level is exceeded for a certain period of time. Here, too, the provisions of Annex <em>SB<\/em> of UL 508A must be <strong>strictly<\/strong> observed.   <\/p>\n\n<h2 id=\"kennzeichnung-der-kurzschlussfestigkeit\" class=\"wp-block-heading\">Short-Circuit Resistance Rating<\/h2>\n\n<p class=\"wp-block-paragraph\">The NEC requires that the short-circuit withstand rating be <strong>clearly<\/strong> marked on all control cabinets. The law does not specify exactly what \u201cclearly visible\u201d means, which is why the marking is often found <strong>inside the control cabinet<\/strong> in an easily visible location. This marking requirement applies regardless of whether a UL label is present.  <\/p>\n\n<figure class=\"wp-block-image size-large is-resized\"><img decoding=\"async\" width=\"1280\" height=\"720\" src=\"https:\/\/krayer.de\/wp-content\/uploads\/2024\/04\/maxresdefault-1.jpg\" alt=\"The interior of a short-circuit-proof control cabinet\" class=\"wp-image-6475\" style=\"width:1239px;height:auto\" title=\"Short-Circuit Current Rating per UL 508A\" srcset=\"https:\/\/krayer.de\/wp-content\/uploads\/2024\/04\/maxresdefault-1.jpg 1280w, https:\/\/krayer.de\/wp-content\/uploads\/2024\/04\/maxresdefault-1-768x432.jpg 768w, https:\/\/krayer.de\/wp-content\/uploads\/2024\/04\/maxresdefault-1-300x169.jpg 300w\" sizes=\"(max-width: 1280px) 100vw, 1280px\" \/><\/figure>\n\n<h2 id=\"wichtig-zu-beachten-regionale-unterschiede\" class=\"wp-block-heading\">Important to Note: Regional Differences<\/h2>\n\n<p class=\"wp-block-paragraph\">This article describes the <strong>Short Circuit Current Rating (SCCR)<\/strong> and the associated requirements for control panels under the <strong>National Electrical Code<\/strong> (NEC). The NEC is a national occupational safety law in the United States. Unlike in Germany, federal law in the U.S. takes a <strong>back<\/strong> seat <strong>to<\/strong> state laws regarding occupational safety, which in turn are subordinate to the regulations of the respective counties or cities. German machinery and plant manufacturers who wish to export to the U.S. should therefore <strong>be sure to familiarize<\/strong> themselves <strong>in advance with regional specifics and variations in short-circuit current resistance (SCCR) testing<\/strong> \u2014or simply partner with an experienced provider such as Krayer.   <\/p>\n\n<p class=\"wp-block-paragraph\"><h2 class=\"wp-block-heading\"><strong>Zusammenfassung<\/strong><\/h2><p class=\"wp-block-paragraph\"><\/p>\n\n<p class=\"wp-block-paragraph\">The SCCR (Short Circuit Current Rating) is the term used to describe the rating of control panels based on their short-circuit current capacity. According to NEC 409, this rating is mandatory for all electrical systems intended for use in North America. In response to the requirements of the 2005 revisions to NEC 409, UL added Appendix SB to the <a href=\"https:\/\/krayer.de\/en\/ul-wissen\/ul-blog\/how-do-ul-508-and-ul-508a-differ\/\">UL 508A standard<\/a>. If components from a single manufacturer are used exclusively during the design and manufacture of a control panel, these components have the same short-circuit withstand capability, which can be verified through a documented test. However, this method, known as \u201cCoordinated Selection,\u201d results in a loss of flexibility. If, however, the control cabinet is built and certified according to UL 508A, components with different short-circuit withstand capabilities can be installed, since Annex SB specifies a short-circuit rating (SCCR) in any case. Nevertheless, regional specifics should always be taken into account when implementing the SCCR.      <\/p>\n\n<p class=\"wp-block-paragraph\"><\/p><\/p>\n","protected":false},"author":4,"featured_media":12715,"template":"","categories":[163],"tags":[165,169,164,167],"class_list":["post-12714","wiki","type-wiki","status-publish","has-post-thumbnail","hentry","category-ul-wiki","tag-certification","tag-standard","tag-ul","tag-ul-508a"],"_links":{"self":[{"href":"https:\/\/krayer.de\/en\/wp-json\/wp\/v2\/wiki\/12714","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/krayer.de\/en\/wp-json\/wp\/v2\/wiki"}],"about":[{"href":"https:\/\/krayer.de\/en\/wp-json\/wp\/v2\/types\/wiki"}],"author":[{"embeddable":true,"href":"https:\/\/krayer.de\/en\/wp-json\/wp\/v2\/users\/4"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/krayer.de\/en\/wp-json\/wp\/v2\/media\/12715"}],"wp:attachment":[{"href":"https:\/\/krayer.de\/en\/wp-json\/wp\/v2\/media?parent=12714"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/krayer.de\/en\/wp-json\/wp\/v2\/categories?post=12714"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/krayer.de\/en\/wp-json\/wp\/v2\/tags?post=12714"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}